HY-1310

Addressable Heat Detector

> Convenient wiring: Two-wire, polarity-free
> Reliable communication: Built-in microprocessor, stable performance
> Ultra-low power consumption: Ultra-low monitoring current and alarm current
> Detection performance: Accurate temperature detection by sensitive sensor

Technical Specification

Power

24V DC

Current

Monitoring current: ≤ 120μA

Maximum operating current: ≤ 170μA

Indicator

Red

Polling: Flash 6 seconds

Alarm: Remain lit

Fault: Flash 2 seconds

Product Type

A2R

Alarm Threshold

54°C to 62°C (129°F to 144°F)

Wiring

Two-wire, polarity-free

Addressing Method

Electrical encoder

Address Range

1–254

Communication Distance

≤ 1500 m (4921.26 ft)

Operating Temperature

–10°C to +50°C (+14°F to +122°F)

Storage Temperature

–20°C to +65°C (–4°F to +149°F)

Operating Humidity

≤ 95% RH (no condensation)

Color

White

Dimensions (with base)

Φ 100 mm × 50 mm (Φ 3.00" × 1.50")

Weight (with base)

81 g (0.18 lb)

Certifications

GB 4716-2005

 

Nokta Elektronik ve Bilişim Sistemleri