DRL-48V240W1EN

Lyte II Serisi Din-Rail 240W 48V 5A Power Supply

  • Universal AC input voltage range
  • Built-in constant current circuit for reactive loads
  • High power density
  • Operate from -30°C to +70°C with -40°C Cold Start
  • Reduced no-load power consumption
  • Compliance with DOE VI Energy Standard
  • Compliance to SEMI F47 @ 200Vac 

 

Output

Output Current

5A

Output Voltage

48V
Output Voltage Range 43.2-52.8 Vdc
Output Voltage Adjustment Range 43.2-52.8Vdc
Output Power 240W
Line Regulation ± 0.5% @ 115Vac & 230Vac
Load Regulation ± 0.5%
PARD < 200mVpp @ 0°C to +70°C
< 600mVpp @ -30°C to 0°C
Start up Time 30ms typ. @ 115Vac & 230Vac
Hold up Time 20ms typ. @ 115Vac (100% load)
20ms typ. @ 230Vac (100% load)
Dynamic Response (Ovenshoot & Undershoot O/P Voltage)  ± 10% @ 115Vac & 230Vac input, 10-100% load (Slew Rate: 2.5A/μS, 50% duty cycle @ 5Hz & 10KHz)
Start up with Capacitive 3,000µF Max
Rise Time 30ms typ. @ 115Vac & 230Vac
Input
Input Voltage  100-240Vac 
Input Voltage Range 90-264vVac
Nominal Input Frequency 47-63Hz
Input Current 2.5A typ.
Efficiency at 100% load 90.5% typ. @ 230Vac
Max Inrush Current 40A typ.@230Vac
Mechanical
Case Chassis / Cover Aluminum / SGCC
Indicator Green LED (DK OK)
Cooling System Convection
Input Terminal  3 pins (rated 300V/30A)
Output Terminal  4 pins (rated 300V/20A)
Noise Sound Pressure Level (SPL) < 25dBA
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
Unit Weight 0.62 kg (1.37 Ib)
Dimensions  123.6 x 40 x 117.2 mm
4.87” x 1.57” x 4.61”
Environment 
Vibration (Operating ) IEC 60068-2-6, Sine Wave: 10Hz to 500Hz @ 19.6 m/s² (2G peak); 10 min per cycle, 60 min for X direction
Shock Test (Operating) IEC 60068-2-27, Half Sine Wave: 10G for duration of 11ms; 1 time in X axis
Operating Temperature -30°C to +70°C (-40°C Cold Start)
Storage Temperature -40°C to +85°C
Power De rating > 40°C de-rate power by 1.67 % / °C @115Vac
> 50°C de-rate power by 2.5 % / °C @230Vac
Operating Humidity 20 to 90% RH (Non-Condensing) 
Shock Test (non operating) IEC 60068-2-27, Half Sine Wave: 50G for duration of 11ms; 3 times per direction, 9 times in total
Vibration (non operating) IEC 60068-2-6, Random: 5Hz to 500Hz (2.09G); 20 min per axis for all X, Y, Z direction
Operating Altitude 0 to 5.000 Meters (16,400 ft.)
Pollution Degree 2
Over Voltage Categort II (Compliance to EN 62477-1 OVC III with 2000 meters altitude)
Protections
Overvoltage <64.8V, SELV Output, Latch Mode
Overload / Overcurrent 105 - 150% of rated load current, Auto-recovery
Continuous current limit Mode (Vo>80%)                                                                    
Over Temperature Latch Mode
Short Circuit Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Protection Aganist Shock Class I with Primary Earth connection
Reliability
MTBF > 700,000 hrs. as per Telcordia SR-332
I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time 10 years (230Vac, 50% load @ 40°C)
EMC
Emission CISPR 32, EN 55032, EN 61000-6-4, AS/NZS CISPR32, EN 61204-3
Compliance to FCC Title 47, EN 61000-6-3: Class B 
Immunity EN 55035, EN 61000-6-2
Compliance to EN 61000-6-1
Harmonic Current Emissions IEC/EN 61000-3-2, Class A
Voltage Fluctuation and Flicker IEC/EN 61000-3-3
ESD Immunity IEC 61000-4-2
Radiated Immunity IEC 61000-4-3
EFT IEC 61000-4-4
Surge  IEC 61000-4-5
Conducted Immunity IEC 61000-4-6
Magnetic Field  IEC 61000-4-8
Voltage Dips IEC 61000-4-11
Component Power Supply for general use EN 61204-3

 



Building Automation
Building automation requires an automatic centralized control system. It must be safe from fire sources and have adequate protection from electrical shock in confined areas. Delta offers compact high power density power supplies with universal AC input voltage. They are highly reliable and meet all relevant safety standards for applications within the scope of building automation.

Typical Applications
Escalator & Elevator
HVAC Control 
Access Control
CCTV Surveillance
Automatic Gates
Security System
 

Machine Automation
Machine automation is highly critical in modern factories. Components used in machine automation must be reliable under any rigorous use. Delta’s power supplies are highly efficient for minimizing power loss from power supply units, thus maximizing savings on electricity bills. Some series provide intelligent overload protection in constant current mode, making them suitable for battery charging systems. Our PCBAs are protected against dust or wet conditions in manufacturing environments.

Typical Applications
Robotic Arm
Machine tool
Injection Molding Machine
CNC lathe
 

Renewable Energy 
Renewable power comes from energy sources that can expose power system components to extreme environmental conditions. For example, wind farms in coastal areas are subject to strong winds and sea water. To operate under such conditions, Delta’s power supplies have a wide AC input range, long-life capacitor, and are protected against corrosion and salt spray. Our CliQ M series complies with wind power HVRT standards and are approved for use in offshore locations.

Typical Applications

Wind turbine
Solar Tracker System
 

Process Automation
Process automation at petrochemical plants and waste water treatment facilities involve hazardous processes. These processes require certified equipment in order to ensure safe operation. Delta’s power supply units are certified under major safety standards to support such applications. Also available in a compact range to save space in control cabinets. Our series with backup modules ensures uninterrupted function for critical processes.

Typical Applications
Petrochemicals Plant
Oil Refinery
Waste water treatment
 

Test & Measurement
Delta’s power supplies are ideal for various testing and measurement applications. Available in compact sizes and with versatile configuration options, our multi-output modules are suitable for applications where the measurement demand is high.

Typical Applications
Spectrum Analyzers
Oscillators
AC Power sources
 

Factory Automation
By enhancing manufacturing operations such as wave soldering, automated conveyor systems, and packaging, factory automation improves production speed as well as product detail and quality. Delta’s industrial power supplies are compact, highly efficient, and our PCBAs are protected against dust and wet conditions in manufacturing environments.

Typical Applications
Packaging Machine
Conveyor Systems
Wave Soldering Machine



LED Lighting
Delta’s LED drivers are designed with major international safety standards in mind. Their high efficiency and strong IP66/IP67 design make them essential for modern energy-efficient LED lighting power solutions. Perfect for both indoor and outdoor applications.

Typical Applications
Street Lighting 
Sport Arena Lighting 
Signage
Agricultural Lighting

 

Nokta Elektronik ve Bilişim Sistemleri

Datasheet

Tarih Versiyon Açıklama İndir

4-2-2021

DRL-48V240W1EN

20-4-2021

TR

Kullanım Kılavuzu

Tarih Versiyon Açıklama İndir

4-2-2021

DRL-48V240W1EN

Sertifika

Tarih Versiyon Açıklama İndir

4-2-2021

CE Belgesi

4-2-2021

CCC Belgesi

4-2-2021

EAC Belgesi

4-2-2021

Reach Belgesi

4-2-2021

RoHS Belgesi

4-2-2021

TÜV Belgesi

Teknik Çizim

Tarih Versiyon Açıklama İndir

4-2-2021

DRL-48V240W1EN